Internal Rack Inverters, 6 Output, 180W.

Rack Inverter

 

GENERAL. These economic inverters convert Exchange Battery voltage to 230V AC, for powering small equipment, Routers, Hubs, Data Loggers etc. All models have an output power of 180 watts shared across the six outlets. Output is either by standard UK 13A or Euro SHUKO or IEC (Kettle type) socket.

OUTPUT: 230V OR 115V AC RMS Nominal.  Each output socket is limited to 30W though up to 60W from one socket is possible if the rest are not fully loaded.  Call our help line should you require further explanation. 115V AC RMS are available.

BATTERY DRAIN: A figure of  0.5amp (24V input) and 0.25amp (48V input)  for every 10 watts of output load is a good guide. Connection to the input on all models is via a pair of 6.3mm Fast-On tabs with a separate grounding terminal for the case. The battery must be fused at source.

CAUTION: This adapter is supplied on the basis of the user determining the suitability for the purpose for which it is to be used. Total live to neutral load capacitance must not exceed 0.25uF per socket. Such capacitance is often found in mains filters which are best removed when equipment is run on an inverter driven system.

 

Models available:

    230V AC OUTPUT

Model No.

Rack Type

Socket Type Battery Output
SM5260 ETSI (4N High). 6 x UK (13A) 48V 230V AC RMS, 30W Per Socket
SM5261 ETSI (4N High). 6 x SHUKO 48V 230V AC RMS, 30W Per Socket
SM5262 ETSI (4N High). 6 x IEC (Kettle) 48V 230V AC RMS, 30W Per Socket
   
SM5264 19 Inch (2U+ High) 6 x UK (13A) 48V 230V AC RMS, 30W Per Socket
SM5265 19 Inch (2U+ High) 6 x SHUKO 48V 230V AC RMS, 30W Per Socket
SM5266 19 Inch (2U+ High) 6 x IEC (Kettle) 48V 230V AC RMS, 30W Per Socket
         
SM5268 ETSI (4N High). 6 x UK (13A) 24V 230V AC RMS, 30W Per Socket
SM5269 19 Inch (2U+ High) 6 x UK (13A) 24V 230V AC RMS, 30W Per Socket
    115V AC OUTPUT
SM5340 ETSI (4N High). 6 x UK (13A) 48V 115V AC RMS, 30W Per Socket
SM5341 ETSI (4N High). 6 x SHUKO 48V 115V AC RMS, 30W Per Socket
SM5342 ETSI (4N High). 6 x IEC (Kettle) 48V 115V AC RMS, 30W Per Socket
   
SM5344 19 Inch (2U+ High) 6 x UK (13A) 48V 115V AC RMS, 30W Per Socket
SM5345 19 Inch (2U+ High) 6 x SHUKO 48V 115V AC RMS, 30W Per Socket
SM5346 19 Inch (2U+ High) 6 x IEC (Kettle) 48V 115V AC RMS, 30W Per Socket
         
SM5348 ETSI (4N High). 6 x UK (13A) 24V 115V AC RMS, 30W Per Socket
SM5349 19 Inch (2U+ High) 6 x UK (13A) 24V 115V AC RMS, 30W Per Socket

 

INPUT SPECIFICATION

 

24V INPUT

48V INPUT

Battery:

24V Nominal.

48V Nominal.

Voltage Range:

22-32V.

43.2-64V.

Current, No Load:

0.3A Typical.

0.2A typical.

Current Drawn Per 10W Load

0.5A.

0.2A.

  OUTPUT SPECIFICATION

 

230V AC

Output Voltage:

230V AC RMS plus or minus 10%.

Frequency:

50 Hz nominal, 48-53Hz. or 60Hz nominal, 58-63Hz.

Power, Nominal:

180W total, 30W per socket (Any one socket rated 60W if under total limit).

Power, Short Term:

200 Watts for 2 minutes.

Max Capacitive Load:

0.25uF direct Live to Neutral capacitance PER SOCKET

Output Wave Form:

Quasi sine wave (stepped square wave).

Protection:

Current and temperature limited. External fuse required.

 

 

  115V AC

Output Voltage:

115V AC RMS plus or minus 10%.

Frequency:

50 Hz nominal, 48-53Hz. or 60Hz nominal, 58-63Hz.

Power, Nominal:

180W total, 30W per socket (Any one socket rated 60W if under total limit).

Power, Short Term:

200  Watts for 2 minutes.

Max Capacitive Load:

0.5uF direct Live to Neutral capacitance PER SOCKET.

Output Wave Form:

Quasi sine wave (stepped square wave).

Protection:

Current and temperature limited. External fuse required.

 

 

 

GENERAL

Size:

ETSI or 19" Standard wide x 80mm high x 10mm depth .

Weight:

190g.

Storage Temperature:

-40 to +70C.

Storage Temperature: -20 to +55C.